Skip to content

Plant Governors

This page documents GASTURBM, GOVCLASM, GOVHYDR and GOVNUC, which the family dispatcher has handled directly since 3.79. Before 3.79 they were compiled under no name and RAMSES rejected them in a data file. They model a gas turbine, a classical steam plant, a hydro plant and a nuclear plant.

The TOR sub-record these models are entered with is described on the Governor Models page.

The tor_gasturbm model is a gas turbine governor following a multi-stage combustion model. It captures the compressor, fuel system, combustion chamber delay, and turbine torque characteristic. The name suffix m indicates a modified version.

Speed governor:

The governor error drives a PI controller producing a fuel demand signal. The speed governor uses:

egov=(ωref−ω)/TDSP−STAT⋅Pelece_{gov} = (\omega_{ref} - \omega) / TDSP - STAT \cdot P_{elec}

with saturation limits [MIN, MAX][MIN,\, MAX].

Fuel system and combustion:

The fuel valve position g1 is driven through:

  • A speed governor with gain ZZZZ and lead–lag time constants determined by XXXX, YYYY
  • A fuel flow path through first-order lag TVALVETVALVE
  • Combustion chamber lag TGAZTGAZ

Turbine output:

The turbine mechanical power follows:

Pm=BF2⋅gcomb+AF2P_m = BF2 \cdot g_{comb} + AF2

where gcombg_{comb} is the combustion output through lag TCDTCD.

Additional thermodynamic correction terms involve TFTF (flame lag) and ECRECR (exhaust correction ratio).

Parameters from Fortran source (prm array):

IndexNameDescription
1TDSPSpeed droop time constant (s)
2STATSteady-state gain
3ZZGovernor proportional gain
4XXLead numerator factor
5YYLag denominator factor
6SACCAcceleration constant
7MINMinimum fuel valve position (pu)
8MAXMaximum fuel valve position (pu)
9TVALVEFuel valve time constant (s)
10TGAZCombustion chamber time constant (s)
11TFFlame lag time constant (s)
12ECRExhaust correction ratio
13TCDCompressor discharge time constant (s)
14BF2Turbine power output slope
15AF2Turbine power output intercept (pu)

Implementation details:

  • nbxvar = 10, nbzvar = 4, nbdata = 15, nbaddpar = 1
  • Additional: prm(16) = SETPOINT (initialised from load-flow power)
  • Observables: g2, x4, g1
Show the data record
SYNC_MACH g1 g1
# FP FQ P Q: share of the power-flow injection (FP, FQ) or initial power (P in MW, Q in Mvar)
1. 1. 0. 0.
# SNOM: Nominal apparent power, used as base power in the machine model (MVA)
800.
# Pnom: Nominal active power of the turbine, used as base power for the turbine model (MW)
760.
# H: Inertia constant (s)
3.
# D: Damping coefficient (usually set to zero when the damper windings are modelled) (pu)
0.
# IBRATIO: Field current base ratio I_fB^mac/I_fB^exc (see above) (pu)
0.95
# TYPE_MOD: Parameter format keyword: RL or XT (case-insensitive)
XT
# Xl: Leakage reactance L_l (pu)
0.15
# Xd: d-axis synchronous reactance (pu)
1.1
# X'd: d-axis transient reactance (must be smaller than Xd) (pu)
0.25
# X"d: d-axis subtransient reactance (pu)
0.2
# Xq: q-axis synchronous reactance (pu)
0.7
# X'q: q-axis transient reactance (pu)
*
# X"q: q-axis subtransient reactance (pu)
0.2
# m: Saturation coefficient (set to 0 to neglect saturation)
0.1
# n: Saturation exponent (ignored when m = 0)
6.0257
# Ra: Armature resistance (pu)
0.
# T'do: d-axis open-circuit transient time constant (s)
5.00
# T"do: d-axis open-circuit subtransient time constant (s)
0.05
# T'qo: q-axis open-circuit transient time constant (s)
*
# T"qo: q-axis open-circuit subtransient time constant (s)
0.1
EXC GENERIC1
# IFLIM: OEL field current threshold (pu)
1.8991
# d: OEL timer band, usually negative: timer runs down at rate 1 below IFLIM+d, holds between IFLIM+d and IFLIM (pu)
-0.1
# f: OEL timer charging rate offset above IFLIM
0.
# S: OEL timer charging rate per unit of field overcurrent (1/pu)
1.
# K1: Not used by the code
100.
# K2: OEL gain on (if - IFLIM), negative so that the OEL lowers excitation (pu/pu)
-1.
# L1: OEL timer lower limit and initial value, negative; the OEL acts when the timer exceeds 0 (s)
-11
# L2: OEL timer upper limit (s)
10.
# G: AVR gain (pu/pu)
70.
# TA: AVR lead time constant (s)
10.
# TB: AVR lag time constant (s)
20.
# TE: Exciter time constant (s)
0.1
# L3: Minimum field voltage (pu)
0.
# L4: Maximum field voltage (pu)
4.
# SPEEDIN: PSS input weight: 1 = speed, 0 = active power
1
# KPSS: PSS gain, derivative washout KPSS s/(1+sTw); 0 disables PSS (pu s)
75.
# Tw: PSS washout time constant (s)
15.
# T1: PSS first lead-lag numerator time constant (s)
0.2
# T2: PSS first lead-lag denominator time constant (s)
0.01
# T3: PSS second lead-lag numerator time constant (s)
0.2
# T4: PSS second lead-lag denominator time constant (s)
0.01
# DVMIN: PSS output lower limit (pu)
-0.1
# DVMAX: PSS output upper limit (pu)
0.1
TOR GASTURBM
# TDSP: rate gain of the load reference driven by SETPOINT (1/s)
0.05
# STAT: speed droop (pu)
0.04
# ZZ: constant term of lead-lag denominator, static gain is 1/ZZ
1.0
# XX: lead time constant of governor lead-lag (s)
0.50
# YY: s coefficient of the lead-lag denominator ZZ + YY s; the lag time constant is YY/ZZ (s)
1.0
# SACC: acceleration limit reference of acceleration control loop (pu/s)
1.0
# MIN: minimum fuel demand (pu)
0.0
# MAX: maximum fuel demand (pu)
1.0
# TVALVE: fuel valve time constant (s)
0.05
# TGAZ: fuel system lag time constant (s)
0.40
# TF: second fuel or combustion lag time constant (s)
0.01
# ECR: combustion delay, first-order Pade approximation; must be nonzero (s)
0.01
# TCD: compressor discharge time constant (s)
0.20
# BF2: slope of turbine power versus fuel flow (pu)
1.0
# AF2: intercept of turbine power versus fuel flow (pu)
0.0
;

The tor_govclasm model is a classical thermal governor with a composite control law including deadband, droop, integral control, and combustion dynamics. The name stands for “governor classical model”.

Speed governor with deadband and droop:

The speed error passes through a deadband [DBON,DEADB][DBON, DEADB] before entering a proportional–integral controller. The integral path has saturation at MAXINTMAXINT and gain ALPHAALPHA. The reset time TRESTRES determines the integration rate.

Valve and combustion dynamics:

The valve demand passes through:

  1. A governor integrator with time constant TSMTSM, its rate held inside [VFN, V0][VFN,\, V0]
  2. A first-order lag TFVTFV (valve actuator)
  3. A rate limiter [PVARMIN, PVARMAX][PVARMIN,\, PVARMAX] (with gain GPVARGPVAR) representing fuel response
  4. A combustion/steam chest lag KCRKCR, TCRTCR producing fuel flow
  5. Lower bound: MINFUELMINFUEL
  6. Transport delay TDELAYTDELAY (approximated)
  7. Turbine output through lag TCHTCH with limits [PMIN, PMAX][PMIN,\, PMAX]

Parameters from Fortran source (prm array):

IndexNameDescription
1STATGovernor static characteristic selector
2DEADBDeadband half-width (pu)
3DBONDeadband onset (pu)
4TSMSpeed measurement / filter time constant (s)
5V0Maximum valve opening rate, upper limit on the governor integrator rate (pu/s)
6VFNMinimum valve rate, applied directly as the lower bound, so normally negative (pu/s)
7TFVValve actuator time constant (s)
8VFRFuel flow rate limit (pu/s)
9MAXINTMaximum integral output (pu)
10ALPHAIntegral controller gain
11TRESIntegral reset time (s)
12GOMPGovernor proportional gain
13PVARMAXMaximum power variation rate (pu)
14PVARMINMinimum power variation rate (pu)
15GPVARPower variation gain
16KCRCombustion gain
17TCRCombustion time constant (s)
18MINFUELMinimum fuel flow (pu)
19TDELAYCombustion transport delay (s)
20PMAXMaximum turbine output (pu)
21TCHSteam chest / turbine lag (s)
22PMINMinimum turbine output (pu)

Implementation details:

  • nbxvar = 6, nbzvar = 10, nbdata = 22, nbaddpar = 1
  • Additional: prm(23) = P0 (initialised from load-flow power)
  • Observables: x2, b3, b4
Show the data record
SYNC_MACH g1 g1
# FP FQ P Q: share of the power-flow injection (FP, FQ) or initial power (P in MW, Q in Mvar)
1. 1. 0. 0.
# SNOM: Nominal apparent power, used as base power in the machine model (MVA)
800.
# Pnom: Nominal active power of the turbine, used as base power for the turbine model (MW)
760.
# H: Inertia constant (s)
3.
# D: Damping coefficient (usually set to zero when the damper windings are modelled) (pu)
0.
# IBRATIO: Field current base ratio I_fB^mac/I_fB^exc (see above) (pu)
0.95
# TYPE_MOD: Parameter format keyword: RL or XT (case-insensitive)
XT
# Xl: Leakage reactance L_l (pu)
0.15
# Xd: d-axis synchronous reactance (pu)
1.1
# X'd: d-axis transient reactance (must be smaller than Xd) (pu)
0.25
# X"d: d-axis subtransient reactance (pu)
0.2
# Xq: q-axis synchronous reactance (pu)
0.7
# X'q: q-axis transient reactance (pu)
*
# X"q: q-axis subtransient reactance (pu)
0.2
# m: Saturation coefficient (set to 0 to neglect saturation)
0.1
# n: Saturation exponent (ignored when m = 0)
6.0257
# Ra: Armature resistance (pu)
0.
# T'do: d-axis open-circuit transient time constant (s)
5.00
# T"do: d-axis open-circuit subtransient time constant (s)
0.05
# T'qo: q-axis open-circuit transient time constant (s)
*
# T"qo: q-axis open-circuit subtransient time constant (s)
0.1
EXC GENERIC1
# IFLIM: OEL field current threshold (pu)
1.8991
# d: OEL timer band, usually negative: timer runs down at rate 1 below IFLIM+d, holds between IFLIM+d and IFLIM (pu)
-0.1
# f: OEL timer charging rate offset above IFLIM
0.
# S: OEL timer charging rate per unit of field overcurrent (1/pu)
1.
# K1: Not used by the code
100.
# K2: OEL gain on (if - IFLIM), negative so that the OEL lowers excitation (pu/pu)
-1.
# L1: OEL timer lower limit and initial value, negative; the OEL acts when the timer exceeds 0 (s)
-11
# L2: OEL timer upper limit (s)
10.
# G: AVR gain (pu/pu)
70.
# TA: AVR lead time constant (s)
10.
# TB: AVR lag time constant (s)
20.
# TE: Exciter time constant (s)
0.1
# L3: Minimum field voltage (pu)
0.
# L4: Maximum field voltage (pu)
4.
# SPEEDIN: PSS input weight: 1 = speed, 0 = active power
1
# KPSS: PSS gain, derivative washout KPSS s/(1+sTw); 0 disables PSS (pu s)
75.
# Tw: PSS washout time constant (s)
15.
# T1: PSS first lead-lag numerator time constant (s)
0.2
# T2: PSS first lead-lag denominator time constant (s)
0.01
# T3: PSS second lead-lag numerator time constant (s)
0.2
# T4: PSS second lead-lag denominator time constant (s)
0.01
# DVMIN: PSS output lower limit (pu)
-0.1
# DVMAX: PSS output upper limit (pu)
0.1
TOR GOVCLASM
# STAT: speed droop (pu)
0.04
# DEADB: speed deadband half-width (pu)
0.003
# DBON: deadband switch, 1 = deadband applied, 0 = none
1.
# TSM: valve servomotor time constant (s)
0.10
# V0: maximum valve opening rate (pu/s)
1.0
# VFN: minimum valve rate, applied as given so normally negative (pu/s)
-1.0
# TFV: valve actuator time constant, read but not used (s)
0.30
# VFR: fast-valving rate, never used (fast valving not implemented) (pu/s)
0.5
# MAXINT: upper limit of valve position, fuel flow and reheater state (pu)
1.0
# ALPHA: HP fraction of turbine power
1.0
# TRES: reheater time constant (s)
5.0
# GOMP: intercept valve opening gain on valve position
25.0
# PVARMAX: upper load bound of sliding-pressure setpoint (pu)
0.10
# PVARMIN: lower load bound of sliding-pressure setpoint (pu)
-0.10
# GPVAR: pressure setpoint at zero load (pu)
0.05
# KCR: boiler pressure controller proportional gain
1.0
# TCR: boiler pressure controller integral time (s)
0.20
# MINFUEL: minimum fuel flow (pu)
0.05
# TDELAY: fuel transport delay, Pade approximation (s)
0.30
# PMAX: maximum steam pressure (pu)
1.05
# TCH: boiler steam storage time constant (s)
0.30
# PMIN: minimum steam pressure (pu)
0.05
;

The tor_govhydr model is a simplified hydraulic governor with PI control and a non-linear penstock. It differs from tor_hydro_generic1 in its simplified turbine characteristic and simpler water-column formulation.

PI governor:

x˙2=KI⋅e,x2∈[0,1]\dot{x}_2 = K_I \cdot e, \quad x_2 \in [0, 1] zdemand=KP⋅e+x2z_{demand} = K_P \cdot e + x_2

where the speed error e=P0/ω−Tm−ω⋅STAT+…e = P_0/\omega - T_m - \omega \cdot STAT + \ldots accounts for the droop and steady-state bias.

Penstock (two-lag water column):

TCE1⋅dx3dt=P−x3(1+TCE2/TCE1)T_{CE1} \cdot \frac{dx_3}{dt} = P - x_3(1 + T_{CE2}/T_{CE1})

The turbine mechanical power is computed via an empirical quadratic:

Pm=1.35⋅z−0.7z2P_m = 1.35 \cdot z - 0.7 z^2

derived from the non-linear head-flow curve approximated at initialisation.

Parameters from Fortran source:

IndexNameDescription
1STATSteady-state gain selector
2KPProportional gain
3KIIntegral gain
4TCGovernor/servo time constant (s)
5V0Maximum gate opening rate, upper limit on gate velocity (pu/s)
6VFMaximum gate closing rate, entered as a positive magnitude and applied as −VF-V_F (pu/s)
7TCE2Second penstock time constant (s)
8TCE1First penstock time constant (s)

Implementation details:

  • nbxvar = 4, nbzvar = 4, nbdata = 8, nbaddpar = 1
  • Additional: prm(9) = P0 (initialised from load-flow power)
  • No observables defined (nbobs = 0)
Show the data record
SYNC_MACH g1 g1
# FP FQ P Q: share of the power-flow injection (FP, FQ) or initial power (P in MW, Q in Mvar)
1. 1. 0. 0.
# SNOM: Nominal apparent power, used as base power in the machine model (MVA)
800.
# Pnom: Nominal active power of the turbine, used as base power for the turbine model (MW)
760.
# H: Inertia constant (s)
3.
# D: Damping coefficient (usually set to zero when the damper windings are modelled) (pu)
0.
# IBRATIO: Field current base ratio I_fB^mac/I_fB^exc (see above) (pu)
0.95
# TYPE_MOD: Parameter format keyword: RL or XT (case-insensitive)
XT
# Xl: Leakage reactance L_l (pu)
0.15
# Xd: d-axis synchronous reactance (pu)
1.1
# X'd: d-axis transient reactance (must be smaller than Xd) (pu)
0.25
# X"d: d-axis subtransient reactance (pu)
0.2
# Xq: q-axis synchronous reactance (pu)
0.7
# X'q: q-axis transient reactance (pu)
*
# X"q: q-axis subtransient reactance (pu)
0.2
# m: Saturation coefficient (set to 0 to neglect saturation)
0.1
# n: Saturation exponent (ignored when m = 0)
6.0257
# Ra: Armature resistance (pu)
0.
# T'do: d-axis open-circuit transient time constant (s)
5.00
# T"do: d-axis open-circuit subtransient time constant (s)
0.05
# T'qo: q-axis open-circuit transient time constant (s)
*
# T"qo: q-axis open-circuit subtransient time constant (s)
0.1
EXC GENERIC1
# IFLIM: OEL field current threshold (pu)
1.8991
# d: OEL timer band, usually negative: timer runs down at rate 1 below IFLIM+d, holds between IFLIM+d and IFLIM (pu)
-0.1
# f: OEL timer charging rate offset above IFLIM
0.
# S: OEL timer charging rate per unit of field overcurrent (1/pu)
1.
# K1: Not used by the code
100.
# K2: OEL gain on (if - IFLIM), negative so that the OEL lowers excitation (pu/pu)
-1.
# L1: OEL timer lower limit and initial value, negative; the OEL acts when the timer exceeds 0 (s)
-11
# L2: OEL timer upper limit (s)
10.
# G: AVR gain (pu/pu)
70.
# TA: AVR lead time constant (s)
10.
# TB: AVR lag time constant (s)
20.
# TE: Exciter time constant (s)
0.1
# L3: Minimum field voltage (pu)
0.
# L4: Maximum field voltage (pu)
4.
# SPEEDIN: PSS input weight: 1 = speed, 0 = active power
1
# KPSS: PSS gain, derivative washout KPSS s/(1+sTw); 0 disables PSS (pu s)
75.
# Tw: PSS washout time constant (s)
15.
# T1: PSS first lead-lag numerator time constant (s)
0.2
# T2: PSS first lead-lag denominator time constant (s)
0.01
# T3: PSS second lead-lag numerator time constant (s)
0.2
# T4: PSS second lead-lag denominator time constant (s)
0.01
# DVMIN: PSS output lower limit (pu)
-0.1
# DVMAX: PSS output upper limit (pu)
0.1
TOR GOVHYDR
# STAT: permanent speed droop (pu)
0.04
# KP: PI proportional gain
2.0
# KI: PI integral gain (1/s)
0.5
# TC: gate servomotor time constant (s)
0.10
# V0: maximum gate opening rate (pu/s)
1.0
# VF: maximum gate closing rate, positive, applied as minus VF (pu/s)
1.0
# TCE2: water column numerator time constant, (1 - s TCE2)/(1 + s TCE1) (s)
1.0
# TCE1: water column denominator time constant (s)
5.0
;

The tor_govnuc model is a nuclear plant governor with deadband, droop, integral control, and a non-linear turbine characteristic via GOMP (the gain of the output multiplier). It is structurally similar to tor_govclasm but tailored for the slower, tightly-regulated dynamics of nuclear steam supply systems.

Speed governor:

The speed error passes through a deadband [DBON,DEADB][DBON, DEADB]:

e=deadband(ωref−ω)−STAT⋅(P−P0)e = \text{deadband}(\omega_{ref} - \omega) - STAT \cdot (P - P_0)

The error enters an integrator with rate limits [GRADMIN,GRADMAX][GRADMIN, GRADMAX] (pu/s) filtered through a ramp time TGRADTGRAD. The integrator output xIx_I passes through a servo TSMTSM.

Turbine characteristic with GOMP:

The turbine output is non-linearly mapped through a gain GOMPGOMP:

Pm=min⁡ ⁣(xIGOMP, 1)⋅f(xI)P_m = \min\!\left(\frac{x_I}{GOMP},\, 1\right) \cdot f(x_I)

where the limiter prevents over-power and ff is a piecewise-linear characteristic.

The steam-valve rate is held inside [VFN, V0][VFN,\, V0], then passes the valve actuator lag TFVTFV, the reset lag TRESTRES and GOMPGOMP to produce the final torque. VFRVFR overrides the rate during fast valving, a path the shipped model never takes: the code fixes its selector at 1 and leaves the fast-valving logic unwritten.

Parameters from Fortran source:

IndexNameDescription
1STATGovernor static characteristic selector
2DEADBDeadband half-width (pu)
3DBONDeadband onset (pu)
4GRADMAXMaximum load gradient (pu/s)
5GRADMINMinimum load gradient / unloading rate (pu/s)
6TGRADRamp filter time constant (s)
7TSMServo time constant (s)
8V0Maximum valve opening rate, upper limit on the steam-valve rate (pu/s)
9VFNMinimum valve rate, applied directly as the lower bound, so normally negative (pu/s)
10TFVValve actuator time constant (s)
11VFRValve rate limit (pu/s)
12ALPHAIntegral gain
13TRESReset time constant (s)
14GOMPOutput power gain

Implementation details:

  • nbxvar = 4, nbzvar = 8, nbdata = 14, nbaddpar = 1
  • Additional: prm(15) = P0 (initialised from load-flow power)
  • Observable: TM
Show the data record
SYNC_MACH g1 g1
# FP FQ P Q: share of the power-flow injection (FP, FQ) or initial power (P in MW, Q in Mvar)
1. 1. 0. 0.
# SNOM: Nominal apparent power, used as base power in the machine model (MVA)
800.
# Pnom: Nominal active power of the turbine, used as base power for the turbine model (MW)
760.
# H: Inertia constant (s)
3.
# D: Damping coefficient (usually set to zero when the damper windings are modelled) (pu)
0.
# IBRATIO: Field current base ratio I_fB^mac/I_fB^exc (see above) (pu)
0.95
# TYPE_MOD: Parameter format keyword: RL or XT (case-insensitive)
XT
# Xl: Leakage reactance L_l (pu)
0.15
# Xd: d-axis synchronous reactance (pu)
1.1
# X'd: d-axis transient reactance (must be smaller than Xd) (pu)
0.25
# X"d: d-axis subtransient reactance (pu)
0.2
# Xq: q-axis synchronous reactance (pu)
0.7
# X'q: q-axis transient reactance (pu)
*
# X"q: q-axis subtransient reactance (pu)
0.2
# m: Saturation coefficient (set to 0 to neglect saturation)
0.1
# n: Saturation exponent (ignored when m = 0)
6.0257
# Ra: Armature resistance (pu)
0.
# T'do: d-axis open-circuit transient time constant (s)
5.00
# T"do: d-axis open-circuit subtransient time constant (s)
0.05
# T'qo: q-axis open-circuit transient time constant (s)
*
# T"qo: q-axis open-circuit subtransient time constant (s)
0.1
EXC GENERIC1
# IFLIM: OEL field current threshold (pu)
1.8991
# d: OEL timer band, usually negative: timer runs down at rate 1 below IFLIM+d, holds between IFLIM+d and IFLIM (pu)
-0.1
# f: OEL timer charging rate offset above IFLIM
0.
# S: OEL timer charging rate per unit of field overcurrent (1/pu)
1.
# K1: Not used by the code
100.
# K2: OEL gain on (if - IFLIM), negative so that the OEL lowers excitation (pu/pu)
-1.
# L1: OEL timer lower limit and initial value, negative; the OEL acts when the timer exceeds 0 (s)
-11
# L2: OEL timer upper limit (s)
10.
# G: AVR gain (pu/pu)
70.
# TA: AVR lead time constant (s)
10.
# TB: AVR lag time constant (s)
20.
# TE: Exciter time constant (s)
0.1
# L3: Minimum field voltage (pu)
0.
# L4: Maximum field voltage (pu)
4.
# SPEEDIN: PSS input weight: 1 = speed, 0 = active power
1
# KPSS: PSS gain, derivative washout KPSS s/(1+sTw); 0 disables PSS (pu s)
75.
# Tw: PSS washout time constant (s)
15.
# T1: PSS first lead-lag numerator time constant (s)
0.2
# T2: PSS first lead-lag denominator time constant (s)
0.01
# T3: PSS second lead-lag numerator time constant (s)
0.2
# T4: PSS second lead-lag denominator time constant (s)
0.01
# DVMIN: PSS output lower limit (pu)
-0.1
# DVMAX: PSS output upper limit (pu)
0.1
TOR GOVNUC
# STAT: speed droop (pu)
0.04
# DEADB: speed deadband half-width (pu)
0.005
# DBON: deadband switch, 1 = deadband applied, 0 = none
1.
# GRADMAX: upper clamp on load reference error, ramp rate is GRADMAX/TGRAD (pu)
0.02
# GRADMIN: lower clamp magnitude, positive, applied as minus GRADMIN (pu)
0.02
# TGRAD: load reference ramp time constant (s)
10.0
# TSM: valve servomotor time constant (s)
5.0
# V0: maximum valve opening rate (pu/s)
1.0
# VFN: minimum valve rate, applied as given so normally negative (pu/s)
-1.0
# TFV: valve actuator time constant, read but not used (s)
0.50
# VFR: fast-valving rate, never used (fast valving not implemented) (pu/s)
0.10
# ALPHA: HP fraction of turbine power
1.0
# TRES: reheater (moisture separator) time constant (s)
20.0
# GOMP: intercept valve opening gain on valve position
1.0
;